SMART I/O User’s Manual
October 01, 1996
©1996 PEP Modular Computers GmbH
Page 5 - 126
Chapter 5 Analog Modules
O_DISABLE_CONV: This operate call tells ISaGRAF to disable the
conversion of a particular channel of a connected
SM-DAC1 module. The syntax is as follows:
<analog var> := OPERATE(<iovar>, O_DISABLE_CONV, 0);
where <analog var> represents the analog return variable and can
be zero if the operate call is supported and the
correct <iovar> is passed or non-zero if an
error occurred.
<iovar> is the variable name for the channel where the
operate call is to take effect.
O_GET_LINE_STATE:
This operate call allows the user to check the line
state on the current version of the SM-DAC1. The
syntax is as follows:
<analog var> := OPERATE(<iovar>, O_GET_LINE_STATE,
<var>);
where <analog var> represents the analog return variable and is
zero if an open loop is detected. Otherwise it
returns 1.
<iovar> is the variable name for the channel where the
operate call is to take effect.
<var> is not used.